Bus Plug Becomes Rat Hotel

April 25th, 2011 Comments off

 

Cutler Hammer 400 Amp Bus Plug

Cutler Hammer 400 Amp Bus Plug

It would be more accurate to say the Square D bus plug became a mouse hotel, but Rat Hotel sounds more dramatic. MIDWEST field services runs into some pretty bizarre circumstances. Some funny, some tragic, and some a little of both. In this case MIDWEST was called to replace a Cutler Hammer 400 amp bus plug that had smoked, code for faulted with some arcing and smoking action. The location was a storage warehouse, damp, with minimum heat. It was easy to spot the damaged bus plug because it was partially discolored, or maybe the dust all over it was just toasted. When MIDWEST opened the bus plug to see how much damage there was and to get the exact catalog number, they discovered the remains of a mouse hotel, or colony, or habitat. A smelly little mess. Apparently mice got into the bus plug through an unplugged knockout on the top side of the old bus plug. It wouldn’t make any difference if this was a 400 amp Squared D bus plug or 400 GE General Electric Bus plug, the problem was caused by the missing knockout closure. A few cents cost a couple thousand dollars before the job was all done. The mice got in through the knockout opening, built nests, and seemed to be doing okay until one of them “crossed the phases,” so to speak. There was one toasted mouse, plus other fatalities, and burnt up debris in the bus plug. The guys removed the bus plug, installed a replacement from MIDWEST’s Switchgear Services, and then brought the damaged bus plug back to the shop. The only remaining problem was finding a volunteer to cleanup and check out the damaged bus plug to see if it was worth full reconditioning.  It wasn’t. Rats

 

Infrared Scanning Bus Plugs when You Can Not Open the Cover

December 10th, 2010 Comments off
 
General Electric AC323R Bus Plug Available from MIDWEST

General Electric AC323R Bus Plug Available from MIDWEST

Sometimes you just can not safely perform an electrical maintenance service per the written specification. For example, in today’s world of real concern for arc flash hazards, safely opening the cover of an energized bus plug, to perform an Infrared Scan, may not be possible. It may not be safely justified because of the high risk. So one argument is whether or not one can actually tell if a bus plug is hot because of overloading or because of a poor connection that is overheating. Is it a load problem or a connection problem?  Is there a problem at all?

Because our Thermographers are all required to work on bus plugs in our switchgear shop, they are very familiar with the interior of most bus plugs. They may have totally reconditioned a specific Square D or Bull Dog 100 amp bus plug. Or they may have repaired many ITE, GE General Electric or Cutler Hammer 60 amp bus plugs. Therefore they know where the interior switch or breaker is located. They may know exactly where the conductors connect to the bus plug feeder terminals.  This knowledge and experience is a big advantage, but the Infrared task is still difficult. The indications of overheating, whether load or connection related, may be very subtle because the interior heat must be re-emitted by the bus plug enclosure, greatly dampening the heat pattern.

Again, knowledge of the bus plug allows the Thermographer to turn art into science, at least to some degree. The thermographer may compare a suspect old bus plug to an identical bus plug nearby. Comparing the feeder conduit helps identify the possible ampacity of an old bus plug.  Comparing the heat pattern of the different plane surfaces of a suspect old or new Cutler Hammer or Square D bus plug may give additional information to help determine the existence and cause of heating.

 

Our thermographers have special safe ammeters to measure the load on a bus plug feeder, where practical and safe. Knowing the actual load, say on a feeder from an old Federal Pacific bus plug, is extremely helpful in determining if the suspected heating is load related or connection related. It is extremely difficult, if even possible, to determine the presence of overheating, much less the cause, by just looking at one plane of the energized bus plug with even a very sensitive Infrared Scanner.

 

It is the combination of the Thermographer’s experience and equipment knowledge that makes scanning energized bus plugs still very useful.  This same experience and knowledge aid in determining the possible cause of a suspected problem manifested by heat.